RX RCBO residual current circuit breaker with integral overcurrent protection
residual current device combined with a circuit breaker, up to 40 A
- Rated currents
- 6; 10; 16; 20; 25; 32; 40 A
- Number of poles
- 2
- Rated conditional short-circuit current
- 10,000 A
Description
RX RCBO residual current circuit breakers with integral overcurrent protection provide disconnection, switching and protection of electrical circuits against earth fault currents, overload and short circuit. They have a time-delayed thermal release for overload protection, an electromagnetic instantaneous release with a plunger (striker) for short-circuit protection, and an electromechanical residual current release that operates without an auxiliary power supply and automatically disconnects the circuit when the earth fault current between phase and earth exceeds the rated residual operating current IΔn.
- standard type for general use in domestic and industrial installations up to 40 A, AC 230/400 V
- for additional protection against direct contact (IΔn 30 mA)
- for protection against indirect contact and to protect buildings, machinery, etc. against fire or short circuit when the insulation of electrical equipment deteriorates (IΔn 100 mA)
- designed for alternating current
- resistant to nuisance tripping caused by various network disturbances
- colour indication of the ON and OFF positions
- bear the mark
- manufactured to STN EN 61 008
Fault type indication
This top-quality product has exclusive features for identifying the fault that occurred in the circuit. A lever in the intermediate position indicates what type of fault may have occurred:
- the circuit breaker lever in the intermediate position indicates a fault in which one of the circuit breaker's releases operated (an overload or short circuit may have occurred),
- the circuit breaker lever and the RCD lever both in the intermediate position indicate a fault in which the residual current release (trip coil) operated because the residual current limit was exceeded (30 mA or 100 mA, depending on the device's rated residual operating current).

Technical data
| Number of poles | 2 |
|---|---|
| Type | AC |
| Rated currents | 6; 10; 16; 20; 25; 32; 40 A |
| Rated voltage | 2P 230 V 50/60 Hz |
| Rated conditional short-circuit current | 10,000 A |
| Rated residual operating current IΔn | 0.03; 0.1; 0.3 A |
| Degree of protection | IP 20 |
| Max. conductor cross-section | 35 mm2 |
| Mounting | DIN rail EN 50 022 |
| Trip indication | red flag indicator |
| Endurance | 10,000 operating cycles |